Legionella detection and subgrouping in water air-conditioning cooling tower systems in Kuwait

Research output: Contribution to journalArticlepeer-review

8 Scopus citations

Abstract

The main aim of the study was to test for the presence of Legionnaires’ disease-causing microorganisms in air-conditioned buildings in Kuwait using molecular technologies. For this purpose, 547 samples were collected from 38 cooling towers for the analysis of Legionella pneumophila. These samples included those from water (n = 178), air (n = 231), and swabs (n = 138). Out of the 547 samples, 226 (41 %) samples were presumptive positive for L. pneumophila, with L. pneumophila viable counts in the positive water samples ranging from 1 to 88 CFU/ml. Of the Legionella culture-positive samples, 204 isolates were examined by latex agglutination. These isolates were predominately identified as L. pneumophila serogroup (sg) 2–14. Using the Dresden panel of monoclonal antibodies, 74 representatives isolates were further serogrouped. Results showed that 51 % of the isolates belonged to serogroup 7 followed by 1 (18 %) and 3 (18 %). Serogroups 4 (4 %) and 10 (7 %) were isolated at a lower frequency, and two isolates could not be assigned to a serogroup. These results indicate the wide prevalence of L. pneumophila serogroup 7 as the predominant serogroup at the selected sampling sites. Furthermore, the 74 L. pneumophila (sg1 = 13; sg3 = 13; sg4 = 3; sg7 = 38; sg10 = 5; sgX = 2) isolates were genotyped using the seven gene protocol sequence-based typing (SBT) scheme developed by the European Working Group for Legionella Infections (EWGLI). The results show that Legionella isolates were discriminated into nine distinct sequence typing (ST) profiles, five of which were new to the SBT database of EWGLI. Additionally, all of the ST1 serogroup 1 isolates were of the OLDA/Oxford subgroup. These baseline data will form the basis for the development of a Legionella environmental surveillance program and used for future epidemiological investigations.

Original languageEnglish
Pages (from-to)10235-10241
Number of pages7
JournalEnvironmental Science and Pollution Research
Volume22
Issue number13
DOIs
StatePublished - 29 Jul 2015

Keywords

  • Cooling tower
  • Kuwait
  • Legionnaires’ disease
  • SBT
  • Serogroups
  • ST profile
  • Water contamination

Funding Agency

  • Kuwait Foundation for the Advancement of Sciences

Fingerprint

Dive into the research topics of 'Legionella detection and subgrouping in water air-conditioning cooling tower systems in Kuwait'. Together they form a unique fingerprint.

Cite this